Stepper motor & encoder

LPC-2.ED1 | Encoder stepper motor driver module

  • Bipolar stepper motor drive outputs (A, B, C, D) with 500 mA or 330 mA drive capability each
  • Internal +24 V DC or external 5 .. 36 V DC stepper motor power supply selection with jumper J6
  • Encoder inputs for incremental or count operation (A, A\; B, B\; Z, Z\)
  • Internal +5 V DC or +12 V DC encoder power supply selection with jumper J1
  • Encoder inputs type (RS-485 or TTL with pull up to +5 V DC) selection with jumpers J3 (A,A\), J4 (B,B\) and J5 (Z,Z\)
  • Standard DIN EN50022-35 rail mounting

USER MANUAL

Differential pressure modules

LPC-2.VV4 | Differential pressure I/O module

  • Differential pressure measurement up to 500 Pa
  • 3 x Voltage analog inputs: 0 .. 10 V
    1 x Voltage analog output: 0 .. 10 V
  • 1 x NTC 10k input
    1 x NTC 10k / voltage analog input: 0 .. 10 V, jumper selectable
  • 8 x Digital inputs
  • 2 x Relay outputs, NO
    2 x Relay outputs, NO / NC, jumper selectable
  • Standard DIN EN50022-35 rail mounting

USER MANUAL

LPC-2.VV1 | Differential pressure sensor module

  • Differential pressure measurement up to 1000 Pa
  • Standard DIN EN50022-35 rail mounting

USER MANUAL

Special digital outputs

LPC-2.SO2 | Power supply module

  • Power supply module with 5.6 .. 12 V DC output for other devices
  • Standard DIN EN50022-35 rail mounting

USER MANUAL

LPC-2.DOL | Door lock output module

  • Door lock open module for 12 V DC low current locks
  • Standard DIN EN50022-35 rail mounting

USER MANUAL

Dimmer outputs

LPC-2.DD2 | Triac dimmer module

  • Triac current drive for dimmable lights or motor drives
  • Operational power supply 100 .. 253 V AC, 50/60 Hz
  • Load current up to 0.9 A
  • Standard DIN EN50022-35 rail mounting

USER MANUAL

LPC-2.DD4 | 4 channel MOSFET dimmer module

  • 4 channel MOSFET dimmer drive for dimmable lights or AC motor fans.
  • Operational power supply 90 .. 264 V AC, 50/60 Hz or 11.5 .. 30 V DC.
  • Overload protected
  • SW adjustable trailing-edge or leading-edge dimmer type, separately for each one of 4 channels.
  • SW adjustable fade-in and fade-out time effect, separately for each one of 4 channels.
  • Phase dependent driver for output which makes this module a lot more resistant to electrical disturbances than commonly used amplitude dependent drivers.
  • Standard DIN EN50022-35 rail mounting

USER MANUAL

LPC-2.PW1 | 4 channel PWM signal output module

  • 4 channel PWM signal output
  • Galvanic isolated outputs
  • 100 mA per output with overload protection
  • Push-pull transistor outputs capable of driving the signal over up to 100 nF capacitance on the lines.
  • Adjustable transition time (fade effect) between various output settings
  • Status LEDs
  • Standard DIN EN50022-35 rail mounting

USER MANUAL

Room modules

LPC-2.R01 | 7DO 6DI room module

  • 7 triac outputs
  • Electrical door lock output
  • 6 voltage free digital inputs
  • Galvanic isolated
  • Flexible inputs for wide use of operation
  • Standard DIN EN50022-35 rail mounting

USER MANUAL

LPC-2.R02 | 4DO 3DI 4AO 2AI room module

  • 4 analog outputs, where Q2 and Q4 may also be used for GND connection (jumper selectable)
  • 2 analog inputs, where I2 input may also be used for NTC or GND connection (jumper selectable)
  • Analog input voltage range: 0 .. 10 V @ ±1 % measurement error of full scale
  • Analog output voltage output range: 0 .. 10 V @ ±1 % accuracy of full scale value
  • Tacho input
  • 3 voltage free digital inputs, galvanic isolated
  • Flexible digital input for wide use of operation
  • 3 snubberless zero crossing triacs output also suitable for use with inductive loads up to 0.9 A
  • 1 snubberless zero crossing triac output also suitable for use with inductive loads up to 3.5 A, with load test function
  • 24 V AC/DC power supply output with overload protection
  • Standard DIN EN50022-35 rail mounting

USER MANUAL